Clamp-on current transformer 5 A

The CLOU clamp-on CT is designed to perform measurements up to 5 A + 20 %. The CT is rated for 600 V ac circuits of Measurement Category III, Pollution Degree 2, per EN/IEC 61010-1 and EN/IEC 61010-2-032.

clamp-on CT 5 A
clamp-on CT 5 A

Specifications

The accuracy classes are related to apparent power. The given accuracy classes are including the internal RS350 error.

Range

current

Accuracy class

5 A

2.4 A ≤ 6 A

0.2

2 A

1.2 A < 2.4 A

0.2

1 A

0.6 A < 1.2 A

0.2

0.5A

0.24 A < 0.6 A

0.2

0.2 A

0.12 A < 0.24 A

0.3

0.1 A

0.05 A < 0.12 A

0.3


Mechanical parameters

Can be uses for wiring diameters

up to ⌀ 8 mm

Max. Jaw opening

10 mm

Dimensions

53 mm x 136 mm x 28 mm

Weight

350 g

Material

PC + ABS + Polycarbonate, UL94 V0


Electrical parameters

Primary current

10 mA – 6 A AC

Max. continuous input current

6 A

Ratio

1000 : 1

Load capacity

≤ 4 Ω

Over voltage category

CAT III 600 V

Frequency range

40 Hz – 3800 Hz

Dielectric strength

3 kV 50 Hz / 60 Hz for 1 minute

Temperature range

-20 °C – +55 °C

Output

2.0 meter cable with connector for RS350

Max. voltage not insulated conductors

600 V

Compliant with Standards

EN/IEC 61010-1, EN/IEC 61010-2-032, IEC60044-1

Clamp-on current transformer 5 A
Rate this post

Published by

Lao Ren

more than 30 years experience in energy metering Product Director Shenzhen CLOU Electronics