Clamp-on current transformer 5 A

The CLOU clamp-on CT is designed to perform measurements up to 5 A + 20 %. The CT is rated for 600 V ac circuits of Measurement Category III, Pollution Degree 2, per EN/IEC 61010-1 and EN/IEC 61010-2-032.

clamp-on CT 5 A
clamp-on CT 5 A


Specifications

The accuracy classes are related to apparent power. The given accuracy classes are including the internal RS350 error.

Range current Accuracy class
5 A 2.4 A ≤ 6 A 0.2
2 A 1.2 A < 2.4 A 0.2
1 A 0.6 A < 1.2 A 0.2
0.5A 0.24 A < 0.6 A 0.2
0.2 A 0.12 A < 0.24 A 0.3
0.1 A 0.05 A < 0.12 A 0.3

Mechanical parameters 
Can be uses for wiring diameters up to ⌀ 8 mm
Max. Jaw opening 10 mm
Dimensions 53 mm x 136 mm x 28 mm
Weight 350 g
Material PC + ABS + Polycarbonate, UL94 V0

Electrical parameters 
Primary current 10 mA – 6 A AC
Max. continuous input current 6 A
Ratio 1000 : 1
Load capacity ≤ 4 Ω
Over voltage category CAT III 600 V
Frequency range 40 Hz – 3800 Hz
Dielectric strength 3 kV 50 Hz / 60 Hz for 1 minute
Temperature range -20 °C – +55 °C
Output 2.0 meter cable with connector for RS350
Max. voltage not insulated conductors 600 V
Compliant with Standards EN/IEC 61010-1, EN/IEC 61010-2-032, IEC60044-1