The CL2030-D has a built-in electronic compensation. The ICTs can be remote controlled by PC. A safety protection by controller is built in. This assures that the secondary side is closed in case of high burden or open circuit. Each ICT will be delivered with a company calibration certificate. A certificate issued by an ILAC accredited laboratory is optional available.

Specs


Specifications ICT CL2030-D

ItemValue
Nominal Current100 A, max. load 120 %
Ratio1 : 1
Ratio error±0.01 % (0.2 A … 120 A)

±0.03 % (0.05 A < 0.2 A)

±0.05 % (0.01 A < 0.05 A)

Phase displacement±0.3’ (0.2 A … 120 A)

± 3’ (0.05 A < 0.2 A)

± 8’ (0.01 A < 0.05 A)

Max. rated secondary voltage0.7 V
Max. rated burden for 10 mA ≤ I < 2 A200 mΩ
Max. rated burden for I ≥ 2 A0.7 V / I
Frequency range45 Hz … 65 Hz
Weight:15 kg

accessories


CLOU control box CL2030-3D-CB
The ICTs can operate stand-alone or together with a remote/control by PC. For remote control with 3rd party equipment a control box CL2030-3D-CB is needed. A interface-description is available on request.

This links are uses to interconnect the primary side of ICTs. The copper links are galvanized. This links are designed to connect ICTs with a center to center distance of min 297 mm and max 317 mm.

FAQ


If you are test equipment manufacturer you can get the ICT2030-D with your company-logo and without any CLOU indication from outside visible.

Category: CL2030

Principally yes, there must be enough space behind the quick connectors and the source must be powerful enough. Please sent us more information, then we can do a proper integration.

Category: CL2030

This contact form is available only for logged in users.

Contact Us

This contact form is available only for logged in users.

Published by

Reinhard Günther

Reinhard Günther

more than 30 years experience in energy metering

Leave a Reply

Be the First to Comment!

wpDiscuz